24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

What is partial discharge inception voltage?

Partial discharge inception voltage is the lowest voltage at which, as the voltage is gradually raised, partial discharges above a defined magnitude threshold are detected. It depends on the defect, on the sensitivity of the measuring system and on the test conditions.

Definition

A partial discharge is a localized electrical discharge that does not completely bridge the insulation: it occurs in a gas void, at a metal point, on a contaminated surface or at an interface. Inception voltage is the value at which discharges appear when the voltage is raised gradually from zero. Extinction voltage is the value at which they disappear when the voltage is reduced after they have started, and it is usually lower than the inception voltage.

Why inception and extinction differ

Starting a discharge in a gas requires a sufficient field and an available initial electron. Once discharges occur, the charges deposited on the walls of the void, the modification of the gas and the heating allow them to continue at a lower field. The difference between the two values is a characteristic of the type of defect.

What the value depends on

  • Type and size of the defect: small or large voids, sharp points or surfaces. The geometry determines the local field.
  • Pressure, gas and temperature: according to Paschen’s law, the voltage needed for a discharge in a gas depends on pressure and distance.
  • Humidity and surface contamination.
  • Sensitivity of the measuring system: if only discharges above a threshold are detected, the apparent inception depends on that threshold and on the background noise.
  • Rate of rise and test duration: initial electrons may take time to appear; a rapid increase overestimates the value.
  • Stress history: insulation that has already had discharges behaves differently from intact insulation.

How to interpret the result

  1. Compare the inception voltage with the operating voltage of the equipment. If it is considerably higher, no discharges are expected in normal service; if it is close or lower, there is a risk of progressive degradation.
  2. Observe the extinction voltage: an extinction below the service voltage means that, once an event has started (for example, an overvoltage), the discharges can be sustained.
  3. Record the phase pattern of the discharges, which helps identify the type of defect.

What an engineer sees in practice

In a noisy field test, values vary between measurements. It is common to repeat the test and to document the sensitivity threshold and the ambient conditions so that the results are comparable.

Safety

Partial discharge tests are carried out at high voltage: they must be performed by qualified personnel, with safety zones, grounding and procedures in accordance with the applicable regulations.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer