Physical idea
A real dielectric polarizes when a field is applied: its bound charges shift or its dipoles orient. Each polarization mechanism has a characteristic time, so it responds to some frequencies and not to others. In addition, conduction by free ions introduces losses that dominate at low frequencies. If the complex capacitance or the dissipation factor is measured at a low voltage over a frequency sweep, the result is a curve with features that reflect these processes.
What is measured
An alternating voltage of moderate amplitude and variable frequency is applied to the insulation terminals, and the capacitance and dissipation factor are determined at each frequency. The result is presented as curves versus frequency. Extending the range toward very low frequencies requires long measurement times, because each cycle lasts a long time.
What it reveals
- Low-frequency region: sensitive to the moisture of the paper and to conductivity. Wet insulation shows higher losses and capacitance in this zone.
- Intermediate region: reflects the interaction between the paper and the oil, and is related to the geometry of the barriers.
- High-frequency region: depends more on the properties of the oil and the structure of the insulation.
With the aid of a geometric model of the insulation, the measured curve is compared with reference curves to estimate the water content of the solid insulation and the conductivity of the oil.
Effect of temperature
The curve shifts toward higher frequencies as temperature increases. The temperature of the insulation during measurement must therefore be known, and the results are corrected or interpreted with a model that incorporates it. Measuring with the equipment in a thermal gradient complicates interpretation.
Advantages and limitations
- It is a non-destructive technique at low voltages, useful for estimating moisture without taking paper samples.
- Interpretation depends on the model, the geometry and the cleanliness of the insulation; results from equipment of different designs are not directly comparable.
- Electromagnetic interference in energized substations affects low-frequency measurements.
Safety
Even though the measurement voltage is low, the instrument is connected to insulation in high-voltage installations: the work must be done by qualified personnel, with the equipment de-energized and grounded, and in accordance with the applicable regulations.