What does IEC 61724-1 contribute to system monitoring?

IEC 61724-1 establishes how to instrument and monitor a photovoltaic system: what to measure, with which sensors, how to log the data and how to calculate indicators such as the performance ratio to compare production against what was expected.

The problem it solves

If a system produces less energy, it is necessary to know whether that is due to less sun or to a real problem. The standard defines a common method for measuring irradiance, temperature, energy and other variables, and for calculating indicators that separate the effect of the solar resource from the performance of the system.

Main indicators

  • Final yield: energy delivered per unit of installed rated power.
  • Reference yield: what the system would have produced if all the irradiance received were converted at the rated efficiency.
  • Performance ratio: the quotient of the two; it indicates what fraction of the theoretical potential was used, taking into account losses from temperature, soiling, wiring and conversion.

Monitoring classes

The standard groups monitoring systems into classes according to accuracy and detail: from basic systems with few variables to high-accuracy systems with redundant sensors and additional measurements. The level required depends on the size of the system and the use of the data, for example a performance guarantee or simple supervision.

What an engineer sees in the field

Data quality depends on the sensors: pyranometers or reference cells in the plane of the modules, module temperature sensors, energy meters and time-stamping data loggers. Data with gaps and dirty or misaligned sensors distort the performance ratio and lead to false conclusions.

How to interpret the ratio

A stable value with seasonal variations is normal, because temperature has an influence. A persistent drop relative to the historical record suggests soiling, string failures, inverter availability or degradation. To decide, review the data by period and by piece of equipment, not just the annual average.

Note on editions

This guide describes only the general scope of the standard. The requirements, the tests and their order change between editions, so consult the current edition and the one required by the contract or the authority.