What makes it different
An underground vault combines two types of risk that reinforce each other: that of a confined space, because of its narrow access and enclosed atmosphere, and the electrical risk from the cables, splices and equipment it houses. It is also usually located on a public roadway, with traffic overhead, and it is prone to flooding.
Characteristic hazards
- Atmosphere: gases entering from the ground or from ducts, such as methane from nearby drains or natural gas from leaks, and oxygen deficiency from oxidation or decomposition. Dense gases settle at the bottom.
- Water and moisture: water in the presence of conductors raises the electrical risk and makes the work difficult.
- Cable and splice failure: a degraded splice can fail with an electric arc, heat and smoke.
- Traffic and falling objects at the access opening.
- Access: a narrow ladder, a heavy cover and no room to maneuver during a rescue.
Work sequence
- Mark off the area and protect the access opening from traffic.
- Open the cover with suitable equipment and let the vault ventilate before looking in.
- Measure the atmosphere from outside and at different levels; use forced ventilation if needed.
- Identify the circuits in the vault and confirm with network operations which ones are de-energized, isolated and grounded; verify the absence of voltage.
- Control the water by pumping, and do not enter if the level or the flow prevents doing so safely.
- Enter with a permit, a harness with a means of extraction from outside, an attendant and communication.
- Maintain continuous monitoring during the work.
What an engineer sees in practice
The most delicate part is usually the decision about the electrical condition. It is not always possible to de-energize everything; when circuits must stay in service, work near live parts is for specialists with specific procedures, and a safe distance and protection against accidental contact are maintained.
When entry does not apply
If the vault cannot be ventilated, if there is water with energized circuits or if the readings are not acceptable, do not enter; correct the condition first. All work in these vaults presents electrical and confined space hazards: it must be done by qualified, authorized personnel, in accordance with current regulations.