Operating principle
The sensor has two small electrically heated beads. The active bead carries a catalyst, so the combustible gas that reaches it oxidizes on it, releases heat and the temperature rises. The reference bead has no catalyst and compensates for ambient effects such as temperature, humidity and pressure. Both are part of a bridge circuit (Wheatstone). When gas burns on the active bead, its resistance changes, the bridge goes out of balance and an electrical signal proportional to the concentration appears.
Conditions for it to work
- It requires oxygen. Without enough oxygen there is no catalytic combustion and the sensor underestimates or fails to detect. That is why it is not suitable for inert atmospheres.
- Flame protection. The sensor operates hot inside a housing with a sintered material that lets gas in but prevents a flame from escaping to the surroundings.
Known limitations
Poisoning and inhibition
Some substances, including certain silicon, sulfur and halogenated compounds, coat the catalyst and reduce its sensitivity. The sensor may still appear normal but respond less than it should. Inhibition, a similar but temporary effect, can occur with high concentrations of certain gases.
Readings at high concentrations
With very rich mixtures, combustion on the element may be incomplete or consume the available oxygen, and the reading may not increase linearly, or may even fall. To avoid misinterpretation, the trend is watched and complemented with the oxygen measurement.
Different response by gas
Each fuel produces a different response. The instrument is calibrated with one gas and the reading for others is corrected with the manufacturer’s factors. Some heavy vapors respond slowly.
How to check that it works
The only reliable way is to expose the sensor to a reference gas in a functional test before use and to calibrate at the established frequency. A sensor that responds slowly or with a low signal to the reference gas is degraded.
When it is not the best option
In atmospheres with little oxygen, with a risk of poisoning or where detection without frequent maintenance is needed, an infrared sensor is usually preferred. Use of these instruments in hazardous atmospheres is the responsibility of trained personnel, in accordance with applicable regulations.