Two different tasks
Cleaning means removing the product and residues. Gas-freeing means eliminating the vapors and gases left in the tank’s air and those still coming off adhered material. Both are needed, and the first determines the second: as long as residues remain, the tank will keep generating vapor.
General sequence
- Empty the liquid product through the designated drains.
- Isolate the tank from lines, pumps and energy sources with blind flanges and lockouts, before opening.
- Displace the vapors. Depending on the product, with steam, water filling, inert gas or forced ventilation.
- Open and ventilate while maintaining precautions against ignition, with equipment suitable for flammable atmospheres.
- Remove sludge and scale, with non-sparking tools and without letting them dry out.
- Measure at several levels, without assuming that one good reading holds for the whole tank.
Vapor re-emission
The most important fact is that the tank “breathes” from its residues. Sludge or scale retains product; when it is stirred, heated or ventilated, the product is released. A tank with good readings can get worse once work starts. That is why measurement is continuous during cleaning.
Cases needing special attention
- Iron sulfides: in tanks that held sulfur-bearing products, these deposits can ignite spontaneously on exposure to air. They are kept wet until removed.
- Inert gas purging: it displaces vapors but leaves the tank without oxygen. Air must then be reintroduced and the oxygen confirmed before entry, or entry must be made with supplied-air respiratory protection.
- Toxic products: it must be confirmed that the toxic gas has dropped to acceptable levels, in addition to the flammability measurement.
When entry is not appropriate
If an acceptable, stable atmosphere cannot be achieved after gas-freeing, entry is made with respiratory protection and the controls for a space with a hazardous atmosphere, or the cleaning method is changed to one that does not involve people entering, such as mechanized or remote cleaning.
Records
Methods, times, readings and who authorized the work are documented. Decisions on method and entry must be made by trained people, in accordance with applicable regulations and the information on the stored product.
This guide is for information only. Work involving electrical hazards, heights or hazardous atmospheres must be carried out by qualified, authorized personnel in accordance with applicable regulations.