The material and its weak point
Insulating gloves are made of elastomers, polymers formed by long, flexible chains bonded to one another. That structure provides elasticity and insulation, but its bonds are sensitive to certain environmental agents.
What sunlight does
Ultraviolet radiation has enough energy to break chemical bonds in the polymer chains. Over time, two things happen: some chains are cut and others become more cross-linked than they should be. The result is a material that is stiffer and more brittle at the surface and loses elasticity.
Microcracks
Hardened rubber cannot withstand the stretching that occurs when the glove is put on. Very fine cracks appear, which at first are only visible when the material is stretched. At one of these cracks the dielectric barrier is thinner, and there may be a path of lower resistance for current.
Agents that act together with light
- Heat: speeds up the aging reactions; a glove left in a vehicle cab in the sun ages much faster.
- Ozone: attacks the double bonds in the rubber and cracks the areas under mechanical strain. It is produced by electrical discharges and some equipment.
- Oils and solvents: swell or soften the material.
- Sustained deformation: folding or stretching the glove during storage concentrates the damage at the creases.
What the engineer sees in practice
- A change in color or a dull appearance on the surface.
- A stiff texture, sometimes with fine crazing.
- Cracks visible when gently stretching the finger area or the cuff.
- Failures in dielectric or air inflation tests, even without obvious damage.
How to avoid it
Keep gloves in their container, in a cool, dry, dark place; do not leave them outdoors during breaks; keep them in their natural shape; and follow the test schedule set by the manufacturer and the regulations. A glove with visible aging is taken out of service.
Work involving electrical risk must be done by qualified personnel, following the applicable regulations.