Arc-rated clothing or ordinary flame-resistant clothing?

Arc-rated clothing is designed and tested to limit heat transfer from an electric arc and not to sustain combustion; ordinary flame-resistant clothing resists flame, but it has not been shown to protect against the energy of an arc.

Two different properties

A flame-resistant garment is evaluated by its reaction to flame: that it ignites with difficulty, self-extinguishes and does not keep burning once the source is removed. An arc garment is evaluated by something different: how much thermal energy it lets through to the skin during a short, high-intensity event. Resisting flame is not the same as protecting against an arc.

How arc protection is tested

Arc tests on materials expose samples or garments to an arc generated in a laboratory and use sensors to measure the heat passing through the fabric. The results are expressed as a thermal protection rating, which is associated with categories or levels. Clothing that passes this test is marked with the corresponding rating. Ordinary flame-resistant clothing does not have this measurement.

Differences you can see in practice

Aspect Arc-rated Ordinary flame-resistant
Evaluated by Arc heat transfer and fabric behavior Flame resistance and self-extinguishing
Marking Shows the thermal protection rating Shows flame properties
Use in tasks with an arc flash hazard This is the suitable type, if its rating is sufficient Must not be assumed suitable

Details that matter in use

  • The system is completed with underwear made of non-melting fibers, because synthetics that melt can stick to the skin.
  • Protection depends on the garment being in good condition: free of fuel stains, without excessive wear and laundered according to the manufacturer.
  • It is worn closed and well fitted, with layers that keep air between them.
  • The garment’s rating must be consistent with the energy calculated in the arc flash study.

How to decide

If the risk analysis identifies an arc flash hazard, clothing with a tested and marked rating is needed, not a garment that is merely flame-resistant. Not even the best garment makes a task safe: it is the last barrier. Work involving an arc flash hazard must be carried out by qualified personnel following the applicable regulations.