How is touch voltage measured on a metal enclosure?

Touch voltage on a metal enclosure is measured between the enclosure and a reference point representing the floor where a person's feet stand, using an instrument with an impedance comparable to that of the human body, because the result from an ordinary voltmeter can be misleading.

What touch voltage represents

If insulation fails and the metal enclosure of a piece of equipment becomes energized, a person touching it is subjected to the potential difference between the enclosure and the floor on which they are standing. With effective grounding, that difference must be small and must disappear quickly because the protection trips.

Why just any voltmeter is not enough

A digital voltmeter has a very high input impedance. If the enclosure is connected to a low-capacity source, for example through capacitive coupling or a broken ground conductor, the voltmeter can show a considerable voltage that in reality does not sustain a dangerous current. Conversely, a measurement can mask a real risk. To assess the risk, instruments or networks that simulate the impedance of the human body are used, so that the reading reflects what a person would feel.

General procedure

  1. Confirm that the instrument works and that its measurement category is suitable.
  2. Choose the reference: an electrode or conductive surface on the floor, placed at the distance where a person would stand, or the reference ground specified by the method.
  3. Connect the instrument between the enclosure and the reference, ensuring good contact on an area free of insulating paint.
  4. Measure with the equipment in normal operation and, where the procedure provides for it, under simulated fault conditions using suitable means.
  5. Record the reading and the conditions.

How to interpret the result

  • A reading close to zero with the equipment in operation indicates a good bond between enclosure and ground.
  • A significant reading suggests poor continuity of the protective conductor, high leakage or an ineffective ground.
  • The acceptable touch voltage depends on how long the fault persists; that is why the protection’s trip time is part of the analysis.

A typical case

A tool with a metal housing and a loose ground conductor gives a low value on an ordinary voltmeter, but a meter that simulates the body reveals an appreciable reading. The practical conclusion is to correct the protective conductor.

These measurements involve energized equipment and must be carried out by qualified personnel following the applicable regulations.