Short answer: test, measure, test
The three-step method protects against the most dangerous error: concluding that a circuit is dead because the instrument showed nothing, when in fact the instrument was not working.
- Test the instrument on a known voltage source, or with its own proving device, to confirm that it indicates correctly.
- Measure on the circuit to be worked on, between each pair of relevant conductors and from each conductor to ground.
- Test the instrument again on the known source to confirm that it did not fail during the measurement.
Why all combinations are tested
A three-phase circuit can have voltage between two phases, between phase and neutral or between phase and ground. If only one combination is checked, an energized phase or a defective ground connection can go unnoticed. Each conductor that will be touched is measured against the others and against ground.
Which instrument to use
- One designed for this function, with the measurement category and voltage range suited to the installation.
- With probes, leads and housing in good condition, and with the prior check completed.
- One that clearly indicates the presence or absence of voltage, preferably with an indication that is unambiguous in the presence of induced voltages.
What the engineer sees in practice
In installations with long cables, or cables running parallel to energized circuits, readings caused by coupling can appear. These are called induced or ghost voltages, and they show up especially with high-impedance instruments. A low reading does not confirm that the circuit is de-energized or that it is safe; its origin must be analyzed. A lower-impedance tester can help tell them apart.
After verifying
Verifying the absence of voltage does not replace prior isolation. It is done after the sources have been opened and locked out, and at medium and high voltage it is supplemented with temporary grounding and with dedicated instruments and hot sticks. The method must be followed by qualified personnel in accordance with the applicable regulations.
When to stop
If the instrument fails the test, if the readings are inconsistent or if the circuit cannot be clearly identified, work stops and the person in charge is consulted.