General idea
Electrical risk decreases with distance from energized parts. Approach boundaries are reference distances, measured from the energized part, used to decide who may enter each zone and what measures are needed. They are described in electrical safety standards for the workplace, such as NFPA 70E, and in the applicable Mexican regulations.
The three limits
- Limited approach boundary: past this point, only qualified personnel or unqualified persons accompanied by a qualified person may enter. It relates to the risk of electric shock.
- Restricted approach boundary: closer still, only qualified personnel may enter, with specific measures such as work planning and insulating equipment, because the risk of contact or of arcing between energized parts and the body increases.
- Arc flash boundary: the distance at which an unprotected person could suffer a curable burn from the thermal energy of an arc. Within it, arc flash protection is required.
What they depend on
The first two are determined by the voltage level of the equipment and the type of conductor or exposed part. The arc flash boundary comes from the arc flash study: it depends on the fault current, the clearing time of the protection and the equipment configuration, and it can be larger or smaller than the others.
How it is used in practice
- Identify the equipment’s boundaries on its label or in the study.
- Mark off the zone with barriers or signage.
- Verify the qualification of each person entering and the protection required at each boundary.
What to consider
The distances in the standards change between editions, and the equipment label may be out of date if the installation has changed. The current edition of the applicable standard must be consulted.
Work near energized parts must be carried out only by qualified personnel, in accordance with the applicable regulations and safety procedures.