What it measures
The symbol ΔT indicates a temperature difference. In thermography it is usually the rise of a point above something taken as normal. Its advantage is that it reduces the effect of errors that affect both measurements equally and of common ambient conditions.
Most commonly used references
- Against similar components: the same connection on another phase, or an identical bearing on a twin machine, at similar load. This is the most robust comparison.
- Against ambient: temperature rise relative to the air around the equipment. It shows how much the equipment heats up, but it depends on the ambient temperature.
- Against history: variation from an earlier image of the same point, useful for trends if the conditions were recorded.
Why it must be tied to load
In electrical connections, the power dissipated grows with the square of the current, and so does the ΔT. The same defect gives a small ΔT at low load and a large one at high load. That is why a ΔT without its reference current is incomplete data. Some programs adjust or normalize the ΔT to a reference load, but with caution, because the real relationship depends on the type of defect.
How it is used to prioritize
Many maintenance programs classify findings by ΔT ranges, associating each range with an intervention priority. The values of those ranges are defined by each organization or by the standard it adopts; there is no universal table, and no figures are given here. It is also advisable to consider the criticality of the equipment, the trend, and the type of component, not just the number.
How to interpret the result
- A high ΔT at low load is more worrying than the same value at high load.
- A small ΔT does not rule out a defect if the load was low.
- Absolute temperature matters when it approaches the material’s limit.