Which components are checked
On a transmission line, the critical points are the joints: conductor splices, suspension and dead-end clamps, connectors on taps, and equipment terminals. A contact with high resistance heats up with current, as in any electrical connection. Insulators are also observed, where an abnormal thermal pattern can indicate leakage currents.
What makes this application different
- Distance: targets are small and far away. For them to fill several pixels, telephoto lenses and cameras with good resolution are used.
- Atmospheric attenuation: over long distances, humidity and particles absorb part of the radiation; distance and ambient conditions must be entered into the camera.
- Wind: it cools the conductor and reduces differences, so a defect may stay hidden.
- Load: since heating grows with current, the inspection must be done with sufficient, recorded load.
- Sun: solar heating and reflections on metal complicate interpretation, so hours of lower insolation are preferred.
How the survey is done
It can be on foot or by vehicle on accessible sections, or by helicopter or drone to cover long, hard-to-reach sections. The component is viewed from different angles, compared with similar phases and structures, and its exact location is recorded so that it can be found again.
What is interpreted
- A splice hotter than the adjacent conductor points to a contact problem.
- A clamp that is hot compared with those on the other phases, at the same current, is suspect.
- A conductor that is hot along its entire length indicates a load cause, not a localized defect.
Work near energized lines involves high electrical risk. It must be done by qualified personnel, observing the safety distances and procedures set by applicable regulations.