The mechanism
Contact between two conductors is not a continuous surface: it occurs at small, real bearing points. When a connection is properly tightened, there are many points and a large effective area, and contact resistance is low. If tightness is lost, the effective area falls and the current concentrates in fewer points. The resistance increases.
The power dissipated in that resistance is P = I²R. That is why the heating grows with the square of the current and concentrates right at the joint, where R is higher than in the rest of the conductor.
Why it tends to get worse
- Heat expands and relaxes the materials, and load and unload cycles loosen the bolts further.
- Overheating accelerates oxidation of the surfaces, and the oxide layer increases the resistance.
- Higher resistance means more heat, which aggravates the problem: it is positive feedback.
- Vibration and dissimilar materials (copper and aluminum) contribute to loosening and corrosion.
What is seen in the thermal image
The hottest point is at the connection, and the temperature falls along the conductor moving away from it. Compare it with the adjacent phase: if all three connections carry a similar current and one looks clearly hotter, the pattern points to a contact problem rather than a load problem. If the whole conductor is equally hot, the cause is usually overload or an undersized cross-section.
How to interpret the result
- The heating depends on the current at the time of the inspection, so the same connection may look normal at low load.
- The measured temperature is that of the visible surface; the temperature of the internal joint is usually higher.
- A finding must be recorded together with the load at the time of the image.
Inspection and correction of connections on electrical equipment must be done by qualified personnel following the applicable electrical safety regulations; retightening on energized equipment is not an acceptable practice.