What each technique measures
A loose connection has higher contact resistance. With current flowing, that resistance dissipates energy as heat. Thermography measures the infrared radiation from the surface and therefore sees that heat. Airborne ultrasound, by contrast, picks up high-frequency sound generated by phenomena such as arcing, corona, and surface discharges. A loose connection that only heats up, without sparking, produces little or no ultrasound.
Comparison
| Aspect | Thermography | Ultrasound |
|---|---|---|
| Phenomenon | Resistive heating | Discharge, arc, leakage |
| Needs load | Yes, the heat depends on the current | Depends on the voltage present |
| Line of sight | Yes, it sees the visible surface | Can pick up through gaps and slots |
| Result | Image with temperatures | Audible signal and level |
When each one is the better choice
- Thermography: busbars, terminals, fuses, and breakers under load, where the defect is resistive and the cover can be opened or there is an infrared window.
- Ultrasound: detection of arcing and partial discharges at medium voltage or in closed equipment with no direct view, and early-stage problems where there is already discharge but little heating.
- Both: when you want to confirm a finding with a second, independent phenomenon, or cover both resistive and insulation defects.
How to interpret disagreement
One technique finding nothing does not rule out the defect: thermography may miss a problem because of low load or a cover hiding the point, and ultrasound may not hear a connection that heats up without arcing. The disagreement indicates which mechanism dominates and what the next check should be.
Both inspections are done on energized equipment, so they must be carried out by qualified personnel, with the protective equipment and procedures required by the applicable electrical safety regulations.