What it is for
Inspecting an energized switchboard with a camera normally requires opening doors or removing covers, which exposes personnel to electrical and arc hazards. The infrared window is installed in the door or cover and lets you see the internal components with the equipment closed.
What it looks like
It consists of a frame holding a material that is transparent to thermal infrared, since ordinary glass blocks it. Many are supplemented with a cap or shutter that is opened only for the inspection, so that the interior stays protected the rest of the time.
Advantages
- Personnel exposure from opening energized equipment is reduced.
- Periodic inspections can be done more often and without interrupting operation.
- Inspection conditions are repeatable, because the viewing perspective is always the same.
What to consider
- Location: it is planned so that the window sits opposite the connections and points to be viewed; not all components will be visible.
- Mechanical and arc resistance: the window is part of the enclosure and must not weaken it. It must be designed and certified for the equipment, and its installation cannot be improvised.
- Transmittance: it lets through only part of the radiation; the measurement must be corrected using the window’s data.
- Field of view: the aperture limits what can be seen and the viewing angle.
- Maintenance: the surface must be kept clean and undamaged.
What an engineer sees in practice
A window with a cap on the front of the switchboard, a label stating the waveband of use, and an inspection procedure that specifies at what distance and from what position to operate the camera.
Installation on equipment and any energized work must be carried out by qualified persons, in accordance with applicable regulations and the equipment manufacturer’s instructions.