What is being looked for
Thermography shows surface temperature. In a motor, that information relates to electrical and mechanical losses: every loss is converted into heat, and the heat leaves through the frame, the bearings and the ventilation.
Conditions
- Motor under representative load, with enough time to stabilize thermally; a motor that has just started does not tell the truth.
- Record of current and load during the shot.
- Clear access, with no guards hiding the surface. Fixed guards and covers limit the view.
Points to check and what each finding suggests
| Area | Possible finding |
|---|---|
| Bearings and end shields | Insufficient or excessive lubrication, wear, misalignment |
| Frame | Heat patterns from overload, voltage imbalance or winding faults seen indirectly |
| Air inlets and outlets, fins | Obstruction, dirt, damaged fan |
| Terminal box and terminals | High-resistance connections |
| Coupling and drive | Misalignment, friction, loose belts |
| Starter, drive and power supply | Heating in cables, contactors and fuses |
How to interpret the result
- Compare with identical motors operating under similar conditions, and with previous shots of the same motor.
- Bear in mind that the internal windings cannot be seen; the frame reflects them with a delay and in attenuated form.
- Relate the finding to the insulation class and the manufacturer’s limits, not to a generic figure.
- Combine with vibration analysis, which detects mechanical problems before they show up as heat.
- Verify that the trend repeats in a second inspection before concluding that a progressive defect exists.
- Note the ambient temperature and room ventilation, because they completely change the frame temperature of a healthy motor.
Checks on energized terminal boxes and power feeds require qualified personnel and the procedures set by applicable regulations.