What is a thermal gradient in a component?

A thermal gradient is the variation in temperature along a component; its shape indicates where heat is generated and how it dissipates, and it makes it possible to tell a localized fault from general heating.

What it is

No component has a single temperature. Heat is generated in one place and spreads by conduction, convection and radiation, so the temperature changes from one point to another. This spatial variation is the thermal gradient. In the image, it appears as the color transition surrounding a hot area.

What the shape of the gradient tells you

  • Steep, localized gradient: the heat source is concentrated and small, such as a connection with high resistance. The maximum temperature is at the point of the fault and drops quickly with distance from it.
  • Gentle, extended gradient: the heating is distributed, for example from overloading of a conductor or an excessive load, and the whole part heats up in a similar way.
  • One-directional gradient starting from a joint: heat leaves the joint and travels along the conductor, a classic sign of resistance in the connection.
  • No gradient where one is expected: this may indicate a measurement problem, such as a reflection or uneven emissivity.

Why the material changes what you see

A good thermal conductor, such as copper, spreads heat quickly and smooths the gradient, so a real hot spot can look less intense on the surface than it is at its origin. An insulator preserves pronounced gradients.

How to interpret the result

  1. Locate the maximum and check whether it coincides with a joint, a contact or a change in cross-section.
  2. Observe how the temperature drops in both directions.
  3. Compare with a similar component under the same load.
  4. Rule out the possibility that the shape is the effect of a reflection or of shade from the sun.

The gradient changes with load and over time: a measurement taken at low load or without steady-state conditions can give a misleading image.