Definition
A camera’s total field of view is divided among its pixels. The instantaneous field of view is the part that corresponds to a single pixel, normally expressed in milliradians. It depends on the size of the detector element and on the focal length of the optics: a telephoto lens reduces the IFOV, and a wide-angle lens increases it.
The size of what a pixel sees
For small angles, the dimension a pixel covers on the object is approximately the IFOV, in radians, multiplied by the distance. Doubling the distance doubles the size of the area. If the object is smaller than that area, the pixel averages the object and the background.
Why it matters for measurement
An object that barely fills one pixel produces a mixed reading, and the temperature is underestimated if the object is hotter than its background. To measure with confidence, the object must cover several pixels in both directions, and manufacturers distinguish detection IFOV from measurement IFOV, which is larger. Detecting is easier than measuring.
An example
Imagine a small connector in a panel at a distance. If the camera shows it as a spot of one or two pixels, you will know something is hot, but the figure will fall below the real value. Moving closer or using a lens with a longer focal length will spread the connector over more pixels and give a more faithful reading.
What to check first
- Calculate the spot size at the working distance and compare it with the object.
- Move closer or change optics when the object is small.
- Do not confuse it with the total number of pixels: two cameras with the same resolution can have different IFOVs because of their optics.