Direct answer
After it is taken, the sample remains a living system: the oil can lose gases, gain moisture and oxidize. Transporting and storing it properly means preserving the conditions at the moment of sampling until it is analyzed.
What can change
- Dissolved gases: these escape through permeable stoppers, plastic or faulty closures, and gases from the air also dissolve into the sample if free space remains. Hydrogen, because of its small size, is lost most easily.
- Moisture: poorly sealed containers or those made of hygroscopic materials absorb it.
- Oxidation and color: light and heat can accelerate changes in the oil.
- Sediments: particles settle or adhere to the walls.
Good practices
- Use the container intended for each analysis and do not transfer the sample from one to another.
- Check the closure and the absence of leaks and bubbles before shipping.
- Protect from the sun and heat sources; opaque or amber packaging helps.
- Avoid extreme temperatures and impacts during shipment; for air transport, confirm that the container tolerates pressure changes.
- Shake or homogenize the sample before analyzing particles or water.
- Identify it with an oil-resistant label and attach the field information.
How long to wait
The sooner it reaches the laboratory the better, especially samples for gases and moisture. The standard or method for each analysis indicates the maximum tolerable time; it should not be improvised.
How to interpret a doubtful result
Unexpectedly low hydrogen values or unexplained high water values can come from the sample and not from the equipment. Keeping the shipping history helps decide whether to resample.