Definition
An ideal dielectric stores electrical energy and returns all of it. A real one returns less: part is converted into heat. The loss tangent, tan delta, is the ratio of the dissipated part to the stored part. It is dimensionless.
Geometric interpretation
In an ideal capacitor, the current leads the voltage by 90 degrees. In a real one, the angle is somewhat smaller, and the difference is called the loss angle, delta. The tangent of that angle is tan delta. It is equivalent to the ratio of the imaginary part to the real part of the complex permittivity, or of the resistive current to the capacitive current in the equivalent model.
Where the losses come from
- Conduction: small currents passing through the material, dominant at low frequency.
- Dipolar relaxation: the work of reorienting dipoles against internal friction; it produces loss peaks at certain frequencies and temperatures.
- Interfacial polarization: movement of charges at boundaries or defects.
- Resonances: at very high frequencies, vibrations of ions or electrons.
Why it is useful
It is sensitive to changes in the condition of the insulation. Moisture, contamination, thermal aging or partial discharges raise the losses, often before any other symptom appears. That is why it is used to diagnose equipment insulation and to classify materials for radio-frequency use, where it should be as low as possible.
What is measured in practice
It is measured with a bridge or an impedance analyzer, at one or several frequencies, by applying a signal to a sample with electrodes. The geometry and the electrodes affect the result, as does temperature. Comparison is valid only if made under the same conditions.
How to interpret the result
A low, stable value indicates a material with little dissipation. An increase with time or temperature suggests degradation. At high frequency, the product of tan delta and frequency determines dielectric heating and the attenuation of transmission lines. Isolated values without frequency and temperature are not comparable.
Notice
Tan delta measurements on high-voltage equipment are performed with the equipment de-energized or with special instruments, and must be carried out by qualified personnel in accordance with applicable safety regulations.