Why a pressure transmitter shows a zero shift

A transmitter's zero shifts because of sensor drift, mounting position, temperature, previous overpressure or a blocked atmospheric reference. External causes are ruled out first, and only then is it adjusted.

What a zero shift means

The transmitter indicates a pressure other than zero when the applied pressure is actually nil, or its zero output does not match the lower range value. It is an error added across the whole scale, which is why it affects every point equally.

Most common causes

  • Mounting position: the fill fluid, or the liquid column at the tap, exerts a pressure that varies with orientation and height. Mounting a transmitter in a position different from the one in which it was calibrated produces a shift that is corrected with a zero adjustment.
  • Previous overpressure: a pressure above the tolerated limit deforms the diaphragm or sensor and leaves a permanent shift.
  • Temperature: zero changes with ambient and process temperature; this effect is characteristic of each sensor.
  • Long-term drift: aging of the sensor and the electronics.
  • Atmospheric reference: in a gauge pressure transmitter, a vent port that is plugged or holds moisture changes the reference and mimics a shift.
  • Settling at the tap: liquid, gas or condensate trapped in the impulse line.

How it is diagnosed

First isolate the transmitter from the process, vent it to atmosphere and observe the reading at rest. If it is stable and other than zero, the shift is in the instrument; if it changes over time, temperature, moisture or a leak is involved. If the shift appears only when installed, the cause lies in the tap or the mounting.

What to do about it

A zero adjustment corrects the shift, but it should only be made with pressure that is truly nil and under stable conditions. An adjustment made without checking the span can hide a damaged sensor. If the zero shifts frequently or after pressure events, the cause must be investigated rather than repeatedly adjusted out.