The key question
Does your application depend on pressure relative to the surroundings, or on the pressure itself? If what matters is the stress on a wall, the thrust of a cylinder or the pressure in a pneumatic or hydraulic line, the natural reference is the atmosphere. If what matters is the thermodynamic state of the gas, absolute pressure is needed.
When gauge pressure is the right choice
- Stress in vessels and piping relative to the outside.
- Pneumatic and hydraulic systems where the actuator works against the atmosphere.
- Pumping pressure and process line pressure in medium and high ranges.
- Hydrostatic levels in open tanks.
When absolute pressure is the right choice
- Vacuum, where the pressure must be expressed independently of the weather.
- Processes where absolute pressure determines properties, such as boiling point, gas density or gas mass flow.
- Barometric pressure measurement.
- Low ranges, where atmospheric variation would be comparable to the signal.
Effect of atmospheric pressure
Atmospheric pressure changes with the weather and with altitude. A gauge sensor vented to atmosphere tracks it and subtracts it, which is good if you want relative pressure, but it means that a change in the weather does not affect its reading. An absolute sensor, by contrast, includes that variation. In a low range, that variation can look like instrument drift even though it is real.
Comparison
| Situation | Natural choice |
|---|---|
| Compressed air line | Gauge |
| Vacuum chamber | Absolute |
| Barometer or altimeter | Absolute |
| Open tank with hydrostatic level | Gauge |
| Gas mass flow from pressure | Absolute |
| Low pressure close to ambient | Depends on whether you want to track or subtract the atmosphere |
An example
A wide-range absolute sensor on a low-pressure line loses resolution, because part of its range is spent representing atmospheric pressure. A lower-range gauge sensor makes better use of its scale.
What the engineer sees
Readings that move with the weather, a zero that does not correspond to zero at atmosphere, or figures that differ from another instrument by exactly atmospheric pressure indicate that references have been mixed. When specifying, always state the type of pressure, not just the range.