Operation in stages
- Process connection. Pressure reaches a diaphragm through a threaded port or flange.
- Sensing element. The diaphragm deforms in proportion to the pressure. That deformation is translated into an electrical signal by silicon or thin-film strain gauges, or by the change in capacitance between a diaphragm and a fixed plate.
- Conditioning. The electronics amplify the signal, compensate for temperature effects, linearize it and convert it into the output signal.
- Output. The most widespread signal in industry is a four to twenty milliampere current loop, which also supplies power over the same two wires. Other outputs are voltage, digital protocols superimposed on the current, or purely digital communication.
Why current is used
A current signal is less sensitive to voltage drop in long cables and to noise than a voltage signal. In addition, a nonzero minimum level makes it possible to detect a broken cable, since the current would fall to zero.
Types
- Gauge: referenced to atmospheric pressure.
- Absolute: referenced to vacuum.
- Differential: measures the difference between two ports.
- With diaphragm seal: for aggressive or high-temperature fluids, by means of a fill fluid.
Operating parameters
The zero sets which pressure corresponds to the minimum output, and the span sets the extent of the range. Many transmitters allow the range to be reconfigured within limits. Other parameters are damping, which filters rapid variations, and thermal compensation.
What the engineer sees
Typical problems are zero drift over time or from changes in mounting position, errors from liquid columns in the impulse lines, the effect of ambient temperature, and overpressure damage that leaves a permanent offset. There are also loop faults, such as wiring shorted to ground, an insufficient power supply or an unsuitable load resistance.
What to check first
When faced with a doubtful reading, confirm the zero with the process isolated and at reference pressure, and check the loop power and wiring before concluding that the sensor has failed.
Electrical work in classified or hazardous areas is carried out by qualified personnel, following the applicable regulations.