The principle
In a liquid at rest, the pressure due to the column is the product of density, gravity and height. If that pressure is measured at the bottom, or at a known depth, and the density is known, the height of the liquid above the sensor is obtained. It is an indirect method: the sensor measures pressure, and the level is a calculation.
Configurations
- Open tank. The sensor, submerged or mounted at the bottom, measures the pressure of the liquid plus atmospheric pressure. To eliminate atmospheric pressure, a gauge sensor referenced to the air is used. In submersible probes this means a cable with a vent tube.
- Closed or pressurized tank. The pressure above the liquid is added to that of the column. A differential transmitter is used: one port at the bottom and the other at the top, so that the gas pressure cancels out.
Density rules
The pressure-to-height conversion assumes a known density. If the liquid changes in temperature, composition or concentration, the density changes and the calculated level is biased even though the actual level has not moved. A layer of foam, suspended solids or stratification also alters the relationship.
What needs to be configured
- The density of the liquid at operating conditions.
- The position of the sensor relative to the bottom or to the zero-level reference.
- The range, in units of height or volume, if the tank geometry is available.
An example
In a water tank at nearly constant temperature, the sensor gives a reliable level. If the same sensor is used for a product whose density varies with concentration, the level measurement shifts with the composition. In that case, what is measured most faithfully is the mass per unit area above the sensor.
Sources of error
- Uncompensated density changes.
- A blocked vent line, or one with moisture, on a submersible sensor.
- Sediment deposits or scale on the diaphragm.
- A zero incorrectly set relative to the mounting position.
How to interpret the result
If two level instruments differ consistently, check the assumed density and the zero reference before doubting the sensor. In electrical installations or with hazardous products, the work must be done by qualified personnel under the applicable regulations.