Definition
When a sensor passes suddenly into a medium at a different temperature, it does not change instantly: it has mass and thermal capacity, and heat must flow to or from it. In a first-order model, the time constant is the time it takes to complete approximately sixty-three percent of the total change. After several time constants, the remaining difference is already very small.
What it depends on
- Mass and thermal capacity of the sensor and its sheath. The greater the mass, the slower the response.
- Resistance to heat flow between the medium and the element. A thick sheath, an air gap or a small exchange surface lengthens it.
- The medium. In a stirred liquid the response is much faster than in still air, because the heat transfer coefficient is higher.
- Fluid velocity. Higher flow speeds up the exchange.
That is why it is not a property of the sensor alone: it is reported for defined test conditions.
What the consequences are
- In calibration. You must wait long enough for the sensor to reach equilibrium with the medium. Reading sooner produces an error that looks like bias.
- In measuring changing processes. A slow sensor averages and attenuates rapid variations, and it lags behind.
- In control. The sensor delay adds to the loop dynamics and can make the loop unstable or slow.
How it is determined
The sensor is immersed in a medium at a different temperature and its response over time is recorded. The time to the characteristic value is taken from the curve, normally in moving water or in air, depending on what is of interest.
An example
An exposed fine-wire thermocouple responds much faster than the same thermocouple inside a thick sheath. If the sheath is added to protect the sensor, the cost is a slower response that must be taken into account when interpreting rapid variations.
How to interpret the result
If a measurement changes steadily and does not seem to settle on a value, compare its trend with the time constant before concluding that the process or the sensor has a fault.