Direct answer
The dew point is the temperature at which the gas becomes saturated with water vapor if it is cooled without changing its pressure or moisture content. Below it, the vapor condenses as droplets or, if the temperature is below the freezing point of water, as frost.
Why it is preferred over relative humidity
Relative humidity depends on the air temperature: the same vapor content gives a different relative humidity when heated or cooled. The dew point, by contrast, directly reflects how much vapor there is. If the gas temperature equals the dew point, the relative humidity is one hundred percent. The greater the difference between the gas temperature and its dew point, the drier the gas is relative to saturation.
The influence of pressure
The dew point of a gas depends on the pressure at which it is measured. In compressed air, a distinction is made between the dew point at line pressure and the one the same air would have on expanding to atmospheric pressure. On expanding, the gas is diluted and the dew point falls. A value without its reference pressure can be misleading.
Why it matters
- In compressed air, condensation corrodes piping, damages tools and contaminates processes.
- In process gases, water can damage catalysts or form hydrates.
- In controlled atmospheres, it determines the risk of condensation on cold surfaces.
How it is measured
Chilled-mirror hygrometers detect the temperature at which condensate appears on a surface. Aluminum oxide or capacitive sensors measure humidity through the change in an electrical property. Sampling carries a lot of weight: tubing that absorbs or releases moisture and outside air leaks can falsify the measurement.
What the engineer sees
A dryer that seems to be working but a measured dew point that does not drop usually reveals desiccant saturation, a line bypass or an inadequate sampling point. Before blaming the equipment, it is advisable to check the sampling system.