Start with the link, not the antenna
Industrial telemetry connects sensors, controllers and hubs in plants, fields and substations. The antenna choice is settled by first answering what band the radio uses, what distance it must cover, where each node is and what obstacles lie in between.
Selection criteria
- Band and matching: the antenna must be designed for the radio band, with good return loss across the whole channel.
- Pattern: a hub receiving from many scattered nodes usually requires an omnidirectional antenna. A point-to-point link between two fixed positions benefits from directional antennas, which add gain and reject interference.
- Polarization: it must match at both ends. In an environment with many reflections the polarization can change, but consistent alignment is still recommended.
- Gain and budget: antenna gain adds to the transmitter power and offsets cable and propagation losses. More gain in an omnidirectional antenna means a narrower vertical beam, and with height differences it can leave out nearby nodes.
- Feed line: a long cable takes away power; its length should be minimized and a low-loss cable chosen.
Conditions in the industrial environment
- Metal structures generate reflections and shadows, so the antenna should be located with a clear view.
- Exposed antennas need materials resistant to weather, corrosion and vibration.
- In atmospheres classified as explosion hazards, equipment must comply with the applicable regulations and be installed by qualified personnel.
What to verify after installation
Measure the return loss of the line and check the received signal level on the actual link. If the level is lower than calculated, check connectors, orientation and obstructions before increasing the power.
When to change approach
If line of sight is impossible, it may be better to install a repeater or change the antenna location than to look for more gain.