Definition
A grounding electrode is the component of the system that is in direct contact with the soil and through which current passes from the electrical circuit into the earth. Everything else in the system, such as the protective conductors and bonds, serves to carry the current to it.
Common types
- Rod or stake. Driven vertically; it takes advantage of depth.
- Plate. A buried metal sheet with a larger contact area.
- Buried horizontal conductor. Useful in shallow soils or soils with a highly conductive surface layer.
- Ring. It surrounds a building or structure.
- Grid. A network of conductors laid out in a mesh, typical of substations, which also controls potential gradients at the surface.
- Concrete-encased electrode. Reinforcing steel or a conductor inside the foundation, taking advantage of the fact that buried concrete is a relatively good conductor because of its moisture.
- Metal piping and buried structures. They can act as electrodes, but their use must be evaluated according to regulations and risk, for example because of compatibility with cathodic protection or services carrying flammable fluids.
What determines its performance
The spreading resistance of an electrode depends on its shape and dimensions and on the resistivity of the surrounding soil. Material and diameter have little influence on that resistance, but they do affect durability and the ability to withstand fault current without excessive heating. Current leaves the electrode and spreads through the soil; most of the potential drop occurs close to it.
How to interpret a value
The resistance of an electrode varies with the moisture, temperature and salts in the soil. The measured value is therefore valid for the conditions of that day, and a measurement in the dry season is usually more representative of the worst case. An electrode must also keep its connection: a good electrode connected through a deteriorated conductor is useless.
Design and installation are the responsibility of qualified personnel, in accordance with applicable regulations. Measurements and work on energized electrical installations must be performed by qualified personnel, in accordance with applicable regulations and site safety procedures.