The problem is lightning, not a 60 Hz fault
A tall metal tower is a preferred strike point. Lightning current has very high-frequency components, so the performance of the system depends on its impedance and on short paths, not only on its low-frequency resistance. In addition, lightning does more than damage the structure: it raises the potential of the entire installation and enters through the cables toward the equipment.
System elements
- Air termination and down conductor. The tower’s own metal structure, if continuous, acts as the down conductor. The antennas must lie within the protected zone of the air terminal.
- Electrode. Normally a ring around the base with radial electrodes and rods. Multiple paths share the current and reduce the impedance. Each tower leg is bonded.
- Equipotential bonding. The tower ring, the shelter, the fence, the electrical service ground and the equipment are connected to one another. Without this bonding, the discharge produces destructive potential differences between them.
- Coaxial cables and waveguides. Their shields are connected to the tower at several points, such as at the top, at the base and at the shelter entrance.
- Single entry panel. All incoming lines, whether power, signal or control, pass through one point where surge protectors referenced to the same bar are installed.
What is measured and what is inspected
The electrode resistance, the continuity between legs, ring and shelter bar, and the condition of the bonds and protectors are verified. Corrosion of the connections at the base and the bonding of the shields are the points with the most failures.
What an engineer sees when it fails
Equipment damaged after a storm despite an acceptable electrode resistance points to potential differences between unbonded grounds, or to lines that entered without protection. The cause is almost always a path that did not pass through the bonding point.
Work at heights and near power lines must be performed by qualified personnel, in accordance with applicable regulations.