Two objectives that must be kept separate
In a laboratory, grounding serves one function for safety and another as a reference for measurements. Safety requires that a fault cause the protection to operate. The reference requires that equipment exchanging signals not sit at different potentials or have currents circulating through its shields. A ground that meets the first requirement may not meet the second.
Verification sequence
- Inspection. Check panelboards, ground bars and bonds, and confirm that the installation matches the drawings.
- Continuity of protective conductors. Measure the resistance between the ground bar and the equipment outlets with a low-resistance instrument.
- Neutral-to-ground bond. Confirm that it exists only at the intended point. A second bond downstream creates parallel paths and currents in the ground conductors.
- Electrode resistance. Measure it with the fall-of-potential method or an equivalent, separating the electrode from the system if the procedure requires it.
- Neutral-to-ground voltage at outlets. An abnormal value under load indicates a voltage drop on the neutral or currents in the ground.
- Currents in ground conductors. With a suitable current clamp, a steady current is a sign of loops or leakage.
- Potential difference between interconnected equipment. Measure between the enclosures or references of two pieces of equipment that share signals.
How to interpret the result
There is no single number that defines a good ground. What you are looking for is consistency: continuous paths, a single neutral-to-ground reference point, no steady currents and small potential differences. If noise persists even with a good electrode resistance, the cause usually lies in the internal distribution: loops, shields or switching power supplies.
When copying a solution does not apply
Isolated or dedicated grounds for sensitive equipment are justified only if they are designed correctly and properly connected to the safety reference. A separate ground without an adequate bond can create dangerous potential differences and noise problems. Measurements and work on energized electrical installations must be performed by qualified personnel, in accordance with applicable regulations and site safety procedures.