Ground resistance is not the impedance the noise sees
Ground resistance is measured with a low-frequency signal and describes how current disperses in the soil. Electronic noise is usually at much higher frequencies, where every conductor has inductance and behaves as an impedance, not as a wire of negligible resistance. A long ground conductor, even with very low resistance, can present a high impedance at those frequencies.
What causes it in practice
- Ground loops. If a piece of equipment is connected to ground by two paths, the potential difference between them drives current through the shield or the signal.
- Common-mode currents. Switching power supplies, variable speed drives and nonlinear loads inject high-frequency currents to ground. They return by unintended paths and generate voltage drops between points assumed to be at the same potential.
- Mixed neutral and ground. A neutral-to-ground bond at the wrong point drives load current through ground conductors.
- Poorly terminated shields. A shield connected with a long braid (pigtail) loses effectiveness at high frequency.
- Lack of equipotentiality. When different pieces of equipment have separate ground references, potential differences appear between them.
What to check first
- Use a clamp meter to measure the current in ground conductors and shields: there should be no appreciable permanent currents.
- Verify that there is only one neutral-to-ground bond, at the proper point.
- Measure the voltage difference between the grounds of equipment that shares signals.
- Check the shield terminations and the length of the bonding conductors.
- Observe the noise with an oscilloscope or analyzer to identify its frequency and relate it to a source.
What reduces it
Short, low-inductance ground paths, a common equipotential reference, filters at the noise sources, signal isolation when the loop cannot be broken, and physical separation of power and signal cables. The safety ground of a piece of equipment must never be removed to eliminate noise. Measurements and work in energized electrical installations must be done by qualified personnel, following the applicable regulations and the site’s safety procedures.