What causes unstable readings when measuring ground resistance?

It is almost always one of three things: extraneous currents flowing in the soil, poor contact of the instrument's auxiliary stakes, or stakes placed within the electrode's zone of influence.

What the instrument is really looking at

A stake-type ground resistance tester injects a test current between the electrode under measurement and a current stake, and measures the voltage drop with a potential stake. The resistance comes from the ratio between the two. Anything that alters the injected current or the measured voltage shows up as a reading that moves.

Most frequent causes

Extraneous currents in the soil

An energized installation can have fault, leakage or return currents flowing through the ground, normally at the grid frequency and its harmonics. If they add to the test signal, the reading oscillates. Many instruments use a test frequency different from that of the grid and filter, but intense noise can still saturate them. Some instruments display a noise alarm.

Poor contact of the auxiliary stakes

In dry, stony or compacted soil, the resistance of the auxiliary stake is high and the test current is reduced or fluctuates. Wetting the soil around the stake, driving it deeper or using several in parallel improves contact.

Stake location

If the potential stake lies within the electrode’s zone of influence, or its zone overlaps with that of the current stake, the voltage it measures does not correspond to a stable reference point. The reading changes greatly when the stake is moved slightly.

Leads and connections

  • Rusty or painted terminals on the electrode.
  • Test leads run parallel and close together, which couple with each other.
  • Leads run over energized or buried conductors that induce signals.

How to diagnose

Move the potential stake along the line between the electrode and the current stake and record the resistance at each position. If the location is correct, a zone appears where the reading hardly changes: a plateau. If it does not appear, the stake spacing is insufficient or the subsoil is not homogeneous. Repeating the measurement with the stake line turned in another direction helps detect buried conductors that distort the result.

What is seen in practice

A reading that drifts slowly usually indicates changing moist soil or polarization. A reading that jumps is usually noise or a poor contact. A reading that differs with each orientation points to nearby buried structures or a very heterogeneous soil.

Measurements and work in energized electrical installations must be done by qualified personnel, following the applicable regulations and the site’s safety procedures.