24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

Why does ground resistance vary with the seasons?

Ground resistance varies with the seasons because soil moisture and temperature change, and these govern its resistivity: it rises in dry spells or frost and falls in the rainy season.

The resistance of an electrode is the product of its geometry and the resistivity of the soil around it. The geometry does not change; the resistivity does, mainly because of two environmental factors.

Moisture

Current in the soil travels through the ions dissolved in the water held in the pores. In the dry season the water decreases and the conductive paths are interrupted, so resistivity rises. After heavy rain the opposite happens. The surface layers react first and most strongly, because they are the ones that dry out or become saturated fastest.

Temperature

As the temperature drops, ions move with more difficulty and resistivity increases. If the water freezes, it stops being an effective electrolyte and resistivity rises sharply. In hot climates, heat promotes evaporation, with an effect similar to that of drought on the surface layer.

The role of depth

Deep layers are shielded from surface variations, so their moisture and temperature are more stable. An electrode that depends on the surface layer varies a great deal; one that reaches deep layers or the water table varies little. That is why it is usually recommended that the main part of the grounding system lie below the zone affected by the seasons.

What the engineer sees

Measurements of the same electrode with the same method at different times of year give different values, without any damage having occurred. A reading that is acceptable in the rainy season may be unacceptable at the end of the dry season. If the design used the resistivity from a single date, the value may not represent the worst case.

How to compare measurements

  • Record the date, recent weather and soil condition with each measurement.
  • Always use the same method and the same probe layout.
  • To verify compliance, consider the least favorable condition or apply a seasonal factor according to the project criteria.

How to tell seasonal variation from damage

Seasonal variation is gradual and cyclical, and it repeats every year; damage from corrosion or a loose connection produces a jump or a trend that is not reversed by the rains. Measurements must be made by qualified people, under the applicable safety regulations.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer