Why do buried electrodes corrode?

Buried electrodes corrode because moist soil acts as an electrolyte: the corrosion can be galvanic from dissimilar metals, or caused by stray currents, soil composition or differences in aeration.

Electrode corrosion is an electrochemical process: the metal loses electrons in one zone (anode) and those electrons are consumed in another (cathode), with the moist soil as the medium that closes the circuit. Without moisture or dissolved ions, the process hardly occurs.

Main causes

  • Galvanic coupling: two dissimilar metals connected and buried form a cell. The less noble one corrodes faster. This is the case with steel, zinc or aluminum joined to copper in the same network.
  • Soil composition: the presence of chlorides, sulfates and acidity increases aggressiveness. A highly conductive soil also tends to be more corrosive.
  • DC stray currents: coming from systems with ground return, such as certain traction systems or nearby cathodic protection. Where the current leaves the metal and enters the soil, the metal dissolves.
  • Differential aeration: zones with different oxygen content, for example one section in wet clay and another in loose soil, form concentration cells.
  • Coating damage: on coated electrodes, a discontinuity concentrates the attack at a small point.

What the engineer sees

On excavation, the metal shows pitting, thinning or layers of corrosion product, often near joints and near the soil surface, where moisture and oxygen change. In measurements, it shows up as a gradual increase in resistance, loss of continuity in a section or erratic values between checks.

Common mistakes

  • Mixing dissimilar materials in the network without considering the galvanic couple.
  • Leaving buried connections unprotected and without an inspection well.
  • Choosing the material without studying the soil.
  • Taking a stable resistance as proof of integrity, when the damage may be localized.

Prevention

It is prevented by selecting materials compatible with the soil, protecting joints, avoiding exposed coating edges and watching for stray currents. Periodic inspection of connections and measurements compared over time detect deterioration. Work on grounding systems of energized installations is for qualified personnel.