Single ground or separate grounds for each system?

Within one installation, a single grounding system is advisable or, if there are several electrodes, they should be interconnected with low impedance; separate grounds with no connection create dangerous potential differences during faults and lightning.

The idea that a "dedicated" ground for electronic equipment protects it from the noise of the power ground is very widespread. However, from the standpoint of both safety and performance, a single or interconnected grounding system is what is recommended.

What happens when they are separated with no connection

During a ground fault or a lightning strike, the power ground rises in potential relative to a distant point. A second ground, with no connection, does not follow that rise. A potential difference appears between the two systems that can:

  • Expose a person who touches two pieces of equipment connected to different grounds.
  • Damage equipment interconnected by signal cables.
  • Produce arcs between conductors of the two systems, when the distance is short.

The soil, moreover, is a common medium: two nearby electrodes are coupled through it, and the current of one affects the potential of the other.

How noise is dealt with

Noise is controlled through design: a well-resolved signal reference, correct shielding, filters, cable separation, isolation transformers or surge protectors. In some cases an insulated reference conductor can be used, connected to the system at a single point. All of these measures preserve the connection with the general system.

When distinct electrodes are justified

When specific electrodes exist because of a process or standard requirement, for example for lightning rods or remote installations, they are interconnected with the rest through low-impedance conductors, or through surge protective devices when a direct connection is not permissible.

How to interpret the problem

If a piece of equipment works better when disconnected from the common ground, what should be sought is the cause of the noise (a circulating current, a bonded neutral, a loop), not keeping the separation. Solutions must comply with the standard in force and be carried out by qualified personnel.