A buried electrode, once covered, is difficult to check. The inspection well solves that problem: it is an access built over the top end of the electrode or over the joint between electrode and conductor, normally made of concrete, polymer or tube, with a cover at floor level.
What it is used for
- Visual inspection: it allows the condition of the connection, corrosion and the integrity of the conductor to be seen.
- Measurement: it offers a point to connect instruments, or to temporarily open the joint to measure an isolated electrode.
- Maintenance: it allows connectors to be tightened and elements to be cleaned or replaced.
- Traceability: it marks where the electrode is and makes it easier to locate years later.
How it should be built
The connection inside the well must remain accessible, with room for tools. The cover must withstand the expected load and be identified. The bottom is usually left unsealed so that the electrode keeps contact with the soil and water can drain, avoiding a permanent puddle around the joints, because standing moisture accelerates connector corrosion.
What is checked inside
- That the connector is tight and free of rust that would make it resistive.
- That the materials are compatible and do not form a galvanic couple in the presence of moisture.
- That the conductor is not damaged at the point where it leaves the soil.
- That there is no buildup of soil, roots or water hindering access.
An example of use
During a periodic check, the resistance of an electrode is measured by opening the connection in the well, after verifying that the system will not be left without protection during the test. If the reading changes from the previous one, the connection in the well is checked first, before questioning the electrode.
Ground connections in energized installations must be opened only by qualified personnel, under the applicable safety regulations.