The clamp-on tester (also called a hook-type tester) is placed around the conductor running down to an electrode. Inside the jaw there are two windings on separate cores, one transmitting and the other receiving.
Operating principle
The first core acts as a transformer: it induces a known alternating voltage in the loop, so that the loop is a single-turn secondary. If the loop is closed, this voltage drives a current. The second core detects that current. The instrument divides the induced voltage by the measured current and displays the total resistance of the loop.
Which loop is being measured
The loop includes the electrode under test, the soil, the set of other electrodes connected in parallel and the conductor joining them. If the rest of the system has a very small total resistance, the reading approaches that of the electrode. If there are few or no other electrodes, the value includes resistances that do not belong to the measured electrode, or the instrument cannot measure.
Conditions for a good result
- There must be a genuine closed loop, with continuous metallic connections.
- The conductor must be centered in the jaw, which must close properly and be clean, because a gap in the core degrades the measurement.
- There must be some separation from other current-carrying conductors.
Sources of error
Stray currents from the grid can interfere if they are greater than the measuring current, although some models filter by frequency. A loose connection in the loop gives variable readings. A typical case of a misleading reading is an electrode with a broken down conductor but another metallic path: the instrument measures the loop and does not detect the electrode defect.
When it is useful
It is fast for periodic inspections and for detecting trends in systems with many interconnected electrodes, for example at towers, substations or poles with a continuous neutral. It does not replace fall-of-potential measurement when an absolute value for the electrode is needed. Work near energized conductors must be done by qualified personnel.