An earth ground tester, or ground resistance meter, applies Ohm’s law to the soil. It generates a current that flows between the electrode under test and an auxiliary current electrode, measures the voltage that this current produces between the electrode and a potential probe, and displays the quotient in ohms.
Why it uses alternating current
Soil conducts through electrolytes. Direct current would cause polarization and electrolysis at the electrodes, distorting the measurement. For that reason the instrument uses alternating current, normally at a frequency different from that of the grid and its harmonics, along with a synchronous detector that ignores noise at other frequencies. This makes it possible to measure even at sites with stray currents at the grid frequency.
Three-pole
The current and potential terminals for the electrode under test share a single connection, or are joined at the instrument itself. The resistance of the lead going to the electrode is included in the reading. With short leads and high ground resistances the error is small, but it becomes relevant when low values are measured or long leads are used.
Four-pole
The instrument has two terminals for the electrode under test: one that delivers the current and another that measures the voltage, carried by separate leads to the electrode. Since almost no current flows through the potential lead, its resistance introduces no drop. The result is a reading free of the effect of the leads.
Differences in use
- The three-pole version is sufficient for grounds of moderate resistance and short leads.
- The four-pole version is preferable for low resistance values, long leads or high-accuracy measurements.
- The four-terminal configuration also makes it possible to measure soil resistivity with the Wenner array.
What influences the measurement
Besides the type of instrument, the result depends on the probe spacing, the contact between the probes and the soil, and the absence of nearby buried metal. Measurements on grounding systems of energized installations must be made by qualified people, under the applicable safety regulations.