A grid can have good resistance to earth and still have a disconnected section that leaves equipment without a fault path. Verifying continuity aims to confirm that each connection point is actually joined electrically to the rest of the system.
The idea behind the method
A reliable reference point is chosen, such as an inspection well or an accessible main connection, and the resistance is measured between it and each of the other accessible points on the grid: taps to equipment, structures, panels and inspection wells. Because the grid has many paths in parallel, the resistance between two points is usually very low, so the differences between measurements are more informative than the absolute value.
Instrument
A low-resistance ohmmeter is used, which injects current at the current terminals and measures the voltage drop at separate terminals (four-wire connection). This configuration eliminates the effect of the test leads and contacts, which would otherwise be of the same order as the measured value.
What is observed
- Similar values between points: the grid appears to be intact.
- One point with a value clearly higher than the others: a loose or corroded connection, or a broken conductor on that tap.
- Several points in one area with high values: a possible break in a section of the grid serving that area.
What to check first
Before suspecting the buried grid, it is advisable to clean the contact surfaces and check the tightness at the connection point, which is the most frequent cause of high values. If the anomaly persists, locating the break may require additional measurements, surface potential surveys or spot excavation.
Limits
The test verifies continuity at a low current. It does not guarantee that the joint will withstand fault current, since a high-resistance connection due to corrosion could pass the test and fail under stress. Measurements on grids of energized installations must be performed only by qualified personnel, in accordance with the applicable safety regulations.