Designing a ground grid is an iterative process: a geometry is proposed, its effects are calculated and it is adjusted until the safety criteria are met. There is no single formula that delivers the final grid from the outset.
1. Gather the input data
- Soil resistivity, with its variation with depth.
- Maximum ground fault current and the time the protection takes to clear it.
- Available area and layout of equipment and structures.
- Characteristics of the surface layer that will cover the ground.
2. Size the conductor
The conductor must withstand the thermal heating produced by the fault current during the clearing time, without melting or damaging its joints, and must also have enough mechanical strength for handling and for its environment. In practice, the thermal criterion is rarely the only one: mechanical robustness and corrosion often require a larger cross section.
3. Define the tolerable limits
The step and touch voltages tolerable by the human body are calculated from the fault time and the resistivity of the surface layer.
4. Propose an initial geometry
A grid of conductors is laid out over the area, complemented by rods at the perimeter and at high-current points, such as transformer neutrals and surge arresters. A denser grid lowers touch voltages; the perimeter concentrates the highest gradients, so step voltage is watched there.
5. Calculate and compare
The grid resistance, potential rise and maximum step and touch voltages are calculated. If they exceed the limits, spacing is reduced, rods are added, the area is enlarged or the surface layer is improved.
How to interpret the result
The critical value is not the resistance itself but the voltages at the surface. A low-resistance grid can fail on touch voltage if there are large differences in spacing. Simplified models assume uniform soil; if the soil is stratified, it is advisable to use more complete models. Equations and limits must be taken from the applicable current guide, not from memory.
The design and construction of grids in power installations are the responsibility of qualified personnel, under the applicable safety regulations.