What is ground potential rise?

Ground potential rise is the potential difference between the grounding system and a point of remote earth, and it results from the current entering the soil multiplied by the resistance of the system.

When a fault drives current into the soil through a grounding system, that system rises in potential relative to a very distant point taken as the zero reference. That difference is called ground potential rise, or GPR.

How it arises

Conceptually it is Ohm’s law applied to the earth: GPR is the current actually dissipated into the soil from the system, multiplied by the resistance of the system to remote earth. The part of the fault current that returns through shield wires, cable shields or neutrals does not enter the soil and does not count in this product. That is why reducing the resistance of the system, or diverting part of the current through other metallic paths, reduces GPR.

Why it matters beyond the system

GPR does not stay inside the installation. Any conductor leaving the system toward an area with a potential close to zero carries that difference with it. This creates transferred potentials in:

  • Metal pipes, rails or fences that cross the boundary.
  • Communication and control cables connected to remote points.
  • Shields and neutrals of circuits feeding neighboring installations.

A person touching one of those elements from a low-potential location is subjected to a significant fraction of the GPR.

What the engineer sees

Typical effects are damage to communication equipment, incorrect protection trips, arcing in the insulation of cables leaving the substation and hazardous voltages on apparently isolated metal elements. GPR is calculated during design and compared with the tolerance limits of equipment and people.

When it is a design problem

A high GPR does not imply that the internal step and touch voltages are unsafe, because inside the grid the potential rises almost uniformly. The risk is concentrated at the boundaries and in the connections to the outside. For the applicable criteria, consult the current standard.

Work near the grounding systems of energized power installations must be performed only by qualified personnel, in accordance with the applicable safety regulations.