Definition and function
A wall bushing, also simply called a bushing, solves a geometric problem: the high-voltage conductor must pass through a metal or concrete wall, the cover of a switchgear enclosure or the tank of a transformer without the voltage jumping to the grounded surface. It must also carry the load current and withstand mechanical stress and the weather.
Main parts
- Central conductor: the rod or cable that carries the current.
- Insulation: porcelain, silicone composite, resin or impregnated paper, which separates the conductor from the grounded body.
- Mounting flange: the metal part that is fixed to the wall or tank and connected to ground.
- Sheds or skirts: on the outer part, they increase the creepage distance to resist contamination and rain.
Condenser type
At high voltages, the field concentrates at the edge of the flange. To spread it out, the insulation includes concentric conductive layers within the material, which form a series of capacitors and distribute the field more evenly. Many of these bushings have a test tap connected to the last layer, which allows capacitance and dissipation factor to be measured without removing the bushing.
How they usually fail
- Moisture entering through deteriorated seals.
- Internal partial discharges due to voids or insulation degradation.
- Surface contamination on the outside.
- Overheating due to loose connections.
- Loss of the insulating medium or of internal pressure.
How they are evaluated
Capacitance and dissipation factor are monitored, along with visual inspection of the oil level or cracks and thermal imaging of the connections. A bushing failure in a transformer can be serious, so its condition is tracked over time.
This guide is for information only. Work involving electrical hazards, heights or hazardous atmospheres must be carried out by qualified, authorized personnel, following the applicable regulations.