What a battery DC system looks like
Many direct current systems in substations and plants are kept floating, that is, with neither pole intentionally connected to ground. A first ground fault therefore does not cause a short circuit or trip protections, and the system keeps operating. The risk is that a second fault on the opposite pole creates a short circuit through ground or falsely operates relays and trips.
What is verified
The insulation of the entire system with respect to ground: batteries, charger, panels, cables and loads. For this reason it is monitored continuously with an installed ground fault detector and checked periodically.
How it is done
- Ground fault detector: a permanently connected device that indicates a decrease in insulation and, in advanced versions, indicates the affected pole and circuit.
- Voltage balance: a voltmeter is used to measure the voltage of each pole to ground. In a well-insulated system, the voltages are evenly balanced; a shift toward one pole signals a ground fault on the other.
- Circuit-by-circuit location: by disconnecting feeders in an orderly way, or by using a clamp device that detects the leakage current, to find the affected circuit without interrupting service.
What must not be done
Applying a high-voltage megohmmeter to a system connected to electronic loads can damage them. Measurement with a test voltage is reserved for circuits isolated from the loads and the charger, using the approved procedure.
Common mistakes
- Grounding a pole by mistake during the measurement.
- Ignoring a ground fault alarm because there is no apparent impact.
- Mistaking leakage through electrolyte on the batteries for a cable fault.
The bank can deliver very high short-circuit currents and the batteries give off flammable gases: use insulated tools and qualified personnel.
These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.