The acceptance criteria for an insulation test are defined before measuring, by combining the requirements of the standard or manufacturer, the equipment's history and the test conditions, and they are documented together with the method.

Why they are defined beforehand

If the criterion is decided after seeing the result, the temptation to adjust it so that the equipment passes is great. Setting it beforehand, in writing, makes the test objective and repeatable, and allows another person to reproduce it.

Where the criteria come from

  • The standard or the equipment specification: the main source for acceptance tests on new equipment.
  • The manufacturer: indicates the test voltages and the minimum values expected for its design.
  • The equipment’s own baseline: commissioning measurements, corrected for temperature.
  • Experience with identical equipment: comparison between similar units, phases or sections.
  • The owner or the project: may impose stricter requirements.

What a good criterion includes

  1. Method and conditions: test voltage, duration, connections, reference temperature, equipment condition.
  2. Absolute criterion, such as a minimum value or the absence of breakdown, when the standard establishes one.
  3. Relative criterion, such as comparison between phases, with the previous measurement or with the trend.
  4. Handling of doubtful results: what is done with a value in the doubtful zone, such as repeating the test after cleaning.

How to interpret the result

A value that meets the minimum but shows a sharp drop from the previous measurement deserves attention even if it technically passes. Likewise, a low value on damp equipment does not imply a permanent failure. The criterion must distinguish between rejection, acceptance and acceptance with follow-up.

When a generic value does not apply

Reference values from general tables are for guidance only. They do not replace the equipment specification, and they must not be applied to a type of insulation other than the one for which they were established.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.