What Causes Discharges in Insulation Cavities?

Discharges in insulation cavities occur because the gas inside the void has lower permittivity and lower dielectric strength than the surrounding solid, so the field in the cavity is higher and the gas ionizes.

The physical reason

A void inside solid insulation contains gas, which has a lower permittivity than the solid. In a set of layers in series subjected to a field, the field is distributed in inverse proportion to permittivity, so the field in the gas ends up higher than in the solid. At the same time, the gas withstands less field than the solid before ionizing. Both effects push in the same direction: the cavity is the first place where the insulation breaks down locally.

What happens in each cycle

When the field in the cavity exceeds the ionization value of the gas, a brief discharge occurs, creating charges on the walls. These charges reduce the field inside the void and the discharge extinguishes. Under AC, as the voltage continues to vary, the field grows again and the discharge repeats, normally near the rising phases of each half-cycle. These discharges do not in themselves cause a short circuit, because the rest of the insulation remains intact, which is why they are called partial.

Where cavities come from

  • Bubbles trapped during manufacturing or during resin curing.
  • Incomplete impregnation in paper or mica insulation.
  • Separation between layers caused by thermal cycling or mechanical stress.
  • Gas formed in oil by overheating or by the discharge itself.
  • Defects in joints and terminations.

Why it matters

Each discharge bombards the walls with ions and electrons and produces chemical by-products, such as ozone and acids, that degrade the material. Over time, the cavity grows and can initiate an electrical tree that ends in failure. The rate of damage depends on the type of material, the voltage and the repetition rate.

How it is identified

These discharges are detected by partial discharge measurement, observing the inception voltage and the position of the pulses relative to the voltage wave.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.