Why Does Wet Insulation Give Low Readings?

Wet insulation gives low readings because water, and above all the ions dissolved in it, opens conduction paths within and on the insulation, increasing the leakage current.

What water changes

Dry insulation has very high resistivity. Pure water is a poor conductor, but in practice it contains salts, acids or contaminants that dissolve in it and produce free ions. These ions carry charge under the electric field, so conduction increases and the measured resistance falls.

Where the water is

  • On the surface: a film of condensation or dew on terminals, bushings or windings, which creates a leakage path. This is the most frequent case and the easiest to resolve.
  • Inside the material: absorbed by cellulose, resins, varnishes or pores in the insulation. This is harder to remove and more serious.

What is seen in the measurement

In dry insulation, the apparent resistance rises over time as the charging and absorption currents decay. In wet insulation, conduction current dominates from the start, so the reading is low and hardly grows. This is why the polarization index of wet insulation approaches unity. The reading is also very sensitive to temperature: as the equipment warms up, the resistance drops more than usual.

What to check first

  1. Was the equipment below the dew point? A machine that cools down in a humid environment condenses water.
  2. Is there surface leakage? Cleaning and measuring with the guard terminal helps separate surface leakage from volume leakage.
  3. Are cables or other equipment connected that contribute leakage?

What to do

If the moisture is on the surface, cleaning and drying are enough. If it is internal, controlled drying with heat and air circulation is used, measuring the resistance periodically until it stabilizes. High voltage must not be applied to wet insulation, because it can damage it.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.