Where the contamination comes from
Outdoor insulators are exposed to the environment. Depending on the surroundings, sea salts, soil dust, cement or minerals, industrial emissions, agricultural residues or bird droppings are deposited. Deposits build up gradually, and faster in coastal or industrial areas or those with little rain.
Why it is only dangerous with moisture
A dry layer of contaminant hardly conducts at all. The risk appears when fog, dew or drizzle wet the surface and dissolve the soluble components, forming a conductive electrolyte. A surface leakage current then flows through the wet film. Heavy rain, by contrast, tends to wash the insulator.
Sequence leading to flashover
- The leakage current heats the film and dries it in the areas where current density is highest, normally near the pin, where the diameter is smallest.
- Dry bands form and concentrate the voltage.
- Small arcs occur between the edges of the dry band.
- If the arcs extend and join, the bridging is complete and a full flashover occurs, tripping the protection.
Why porcelain favors it
Glazed porcelain is a surface that wets easily, so it forms a continuous film. Hydrophobic materials, such as silicone, form separate droplets and perform better.
How it is mitigated
- Scheduled cleaning or washing, sometimes with the line energized, by specialized personnel and methods.
- Hydrophobic coatings applied over the porcelain.
- Insulators with greater creepage distance for severe environments.
- Inspection with leakage or surface discharge measurement to decide when to clean.
Work on energized insulators must be done only by qualified personnel, using approved procedures.