What Does IEC 60085 Classify in the Thermal Rating of Insulation?

The IEC 60085 standard classifies electrical insulation systems by their thermal endurance, assigning a class associated with the maximum continuous service temperature for which they are considered suitable.

What this standard puts in order

Heat is the main cause of insulation aging. So that manufacturers and users understand each other, the standard establishes a system of thermal evaluation and designation: each insulation system receives a class that indicates the temperature level at which it can operate during its expected life.

How the classification works

  • The class is assigned on the basis of service experience or thermal aging tests, in which the material or system is subjected to elevated temperatures and its loss of properties is observed up to an end-of-life criterion.
  • Classes are identified by a designation, historically a letter, which can also be expressed by the temperature value.
  • A distinction is made between the individual insulating material and the complete system, since combined materials can behave differently from each one on its own.

What it means in a machine or transformer

The thermal class defines the temperature limit of the insulation. The designer must ensure that the hottest-spot temperature of the winding, under the expected load and ambient conditions, does not exceed that limit. Operating below it extends service life; operating above it shortens life at an accelerated rate.

What an engineer sees in practice

The insulation class appears on the nameplate of a motor or transformer. It should not be confused with the permitted temperature rise, which is a different quantity: the total limit is the sum of the ambient temperature, the average rise and the hot-spot allowance. Changing the installation environment, ventilation or load alters the available margin.

When it does not apply

The standard classifies; it does not by itself establish the test criterion for a piece of equipment. Consult the current edition and the corresponding product standards.

This guide is for information only. Work involving electrical hazards, heights or hazardous atmospheres must be carried out by qualified, authorized personnel, following the applicable regulations.