What changes between the two
Both look for the same pulses associated with insulation defects, but the conditions are very different, and that determines what can be concluded.
Online
- The equipment operates at its actual voltage and temperature, so defects that depend on load or heating show up as they would in operation.
- It does not require a service interruption, which makes it possible to monitor critical assets and observe their evolution over time.
- The environment is noisy: switching, converters, radio and other installations produce signals that are confused with discharges. Filters, suitable sensors and criteria for separating sources are needed.
- Calibration in picocoulombs is difficult. Results are usually compared as a trend, not as an absolute magnitude.
Offline
- The test object is energized with an independent source at a controlled voltage. The voltage can be raised and lowered to identify the discharge inception and extinction voltages, which are relevant data on severity.
- The circuit can be calibrated and the magnitude expressed in picocoulombs.
- The environment is usually less noisy, or it can be shielded.
- It requires taking the equipment out of service and a source with sufficient power, and it does not always reproduce actual thermal and load conditions.
How to choose
Online detection answers the question of whether there is activity and how it is evolving; offline detection answers how much activity there is and at what voltage it appears. In practice they are combined: online monitoring detects a change and an offline test quantifies it during a scheduled outage.
How to interpret the result
The same defect can show different magnitudes with each method, so they are not compared directly without a correlation procedure.
These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.